Product Info
Cold Climate Vertical Stack Heat Pumps (VSXCs) conceal ducted systems conveniently maximize living space. VSXCs can be hidden in a closet or behind a wall and serve multiple spaces via concealed ductwork. With the introduction of Ice Air’s breakthrough cold climate technology, our line of Vertical Stack Heat Pumps (VSXCs) allow for efficient heat, even on the coldest days. Variable speed technology enables greater cooling efficiency on the warmest days.
Category: New Construction/Replacement VSXC
Products: 8VSXC12
Specifications
| SERIES MODEL # | 8VSXC12 |
| Cooling Capacity 2 (BTU/h) | 11,400 |
|---|---|
| Sensible Capacity 2 (BTU/h) | 9,100 |
| Cooling Capacity Range (BTU/h) | 4,700 – 16,000 |
| SEER2 1 | 13.4 |
| Heating Capacity 3 (BTU/h) | 11,100 |
| Heating Capacity Range 3 (BTU/h) | 4,400 – 17,300 |
| HSPF 1 | 7.7 |
| Voltage | 208 |
| Cooling Mode Power (Watts) | 1,056 |
| Cooling Mode Current (A) | 5.1 |
| Heating Mode Power (Watts) | 806 |
| Heating Mode Current (A) | 3.9 |
| Electric Heat (kW) (Optional) | 1.0 |
| Heating Mode Power + 1.0kW Electric Heat (Watts) | 1,806 |
| Heating Mode Current + 1.0kW Electric Heat (A) | 8.7 |
| MCA (with 1.0kW Electric Heat) | 17.3 |
| MOP (with 1.0kW Electric Heat) | 20 |
| MCA (without Electric Heat) | 11.3 |
| MOP (without Electric Heat) | 15 |
| Airflow (CFM) | 520 |
| LOW AMBIENT PERFORMANCE | |
| Heating Capacity @ 10°F | 10,600 + 3,400 Electric Heat |
| COP @ 10°F | 2.5 |
| Heating Capacity @ 5°F | 9,800 + 3,400 Electric Heat |
| COP @ 5°F | 2.35 |
| Heating Capacity @ -5°F | 8,100 + 3,400 Electric Heat |
| COP @ -5°F | 2.0 |
| Specification Notes: 1. Performance data according to CAC/HP AHRI 210/240 standard. 2. Rated performances in cooling mode @ 80°F/67°F DB/WB Indoors and 95°F/75°F DB/WB Ambient. 3. Rated performances in heating mode @ 70°F/60°F DB/WB Indoors and 47°F/43°F DB/WB Ambient. 4. Unit without electric heat will operate below -5°F with derated performance. Performance below -5°F has not been certified. 5. For use as a complete assembly only. For replacement unit applications, consult Manufacturer. |
|