VSXC

Product Info

Cold Climate Vertical Stack Heat Pumps (VSXCs) conceal ducted systems conveniently maximize living space. VSXCs can be hidden in a closet or behind a wall and serve multiple spaces via concealed ductwork. With the introduction of Ice Air’s breakthrough cold climate technology, our line of Vertical Stack Heat Pumps (VSXCs) allow for efficient heat, even on the coldest days. Variable speed technology enables greater cooling efficiency on the warmest days.

Category: New Construction/Replacement VSXC
Products: 8VSXC12

Thermostat Options

Ice Air Product VSXC

Specifications

SERIES MODEL # 8VSXC12
Cooling Capacity 2 (BTU/h) 11,400
Sensible Capacity 2 (BTU/h) 9,100
Cooling Capacity Range (BTU/h) 4,700 – 16,000
SEER2 1 13.4
Heating Capacity 3 (BTU/h) 11,100
Heating Capacity Range 3 (BTU/h) 4,400 – 17,300
HSPF 1 7.7
Voltage 208
Cooling Mode Power (Watts) 1,056
Cooling Mode Current (A) 5.1
Heating Mode Power (Watts) 806
Heating Mode Current (A) 3.9
Electric Heat (kW) (Optional) 1.0
Heating Mode Power + 1.0kW Electric Heat (Watts) 1,806
Heating Mode Current + 1.0kW Electric Heat (A) 8.7
MCA (with 1.0kW Electric Heat) 17.3
MOP (with 1.0kW Electric Heat) 20
MCA (without Electric Heat) 11.3
MOP (without Electric Heat) 15
Airflow (CFM) 520
LOW AMBIENT PERFORMANCE
Heating Capacity @ 10°F 10,600 + 3,400 Electric Heat
COP @ 10°F 2.5
Heating Capacity @ 5°F 9,800 + 3,400 Electric Heat
COP @ 5°F 2.35
Heating Capacity @ -5°F 8,100 + 3,400 Electric Heat
COP @ -5°F 2.0
Specification Notes:
1. Performance data according to CAC/HP AHRI 210/240 standard.
2. Rated performances in cooling mode @ 80°F/67°F DB/WB Indoors and 95°F/75°F DB/WB Ambient.
3. Rated performances in heating mode @ 70°F/60°F DB/WB Indoors and 47°F/43°F DB/WB Ambient.
4. Unit without electric heat will operate below -5°F with derated performance. Performance below -5°F has not been certified.
5. For use as a complete assembly only. For replacement unit applications, consult Manufacturer.