Product Info
The Ice Air RSNU-HP line is a high-performance heat pump with electric heat, specifically designed for new construction projects. Built for durability and quiet operation, this unit delivers superior comfort while meeting today’s highest energy efficiency standards. The use of R-32 Green refrigerant not only enhances performance but also reduces environmental impact, supporting sustainability goals across a wide range of building types.
Engineered for ease of installation and long-term reliability, the RSNU-HP is an ideal solution for developers and contractors seeking all-electric heating and cooling in a compact, user-friendly package. Whether you’re working on multifamily housing, mixed-use buildings, or other large-scale developments, the RSNU-HP provides lasting value and dependable operation in even the most demanding environments.
Category: New Construction PTHP
Products: RSNU07, RSNU09, RSNU13, RSNU16, RSNU18
- PTHP: RSNU-HP – Product Sheet
- PTHP: RSNU-HP – Submittal
- PTHP: RSNU-HP – Dimensional Drawing
- PTHP/PTAC Product Line Brochure
- ICE AIR – Limited Warranty

Specifications
SERIES MODEL # | 5RSNU07-H | 5RSNU09-H | 5RSNU13-H | 8RSNU09-H | 8RSNU13-H | 8RSNU18-H |
Cooling Capacity1 (BTU/h) | 8,400 | 9,000 | 11,600 | 9,600 | 11,900 | 16,600 |
---|---|---|---|---|---|---|
Sensible Cooling Capacity1 (BTU/h) | 6,700 | 7,200 | 9,300 | 7,700 | 9,500 | 11,600 |
EER | 11.6 | 11.4 | 10.6 | 11.2 | 11.0 | 9.5 |
Heating Capacity2 (BTU/h) | 7,600 | 8,700 | 11,600 | 9,300 | 11,600 | 16,000 |
COP | 3.4 | 3.8 | 3.5 | 3.8 | 3.7 | 3.3 |
Voltage | 115 | 115 | 115 | 208/230 | 208/230 | 208/230 |
Electric Heater Power3 (kW) | 1.5 | 1.5 | 1.5 | 3.0 | 3.5 | 3.0 | 3.5 | 4.3 | 3.0 | 3.5 | 4.3 |
Electric Heater Current3 (A) | 13 | 13 | 13 | 14.4 | 16.8 | 14.4 | 16.8 | 20.7 | 14.4 | 16.8 | 20.7 |
Cooling Mode Current (A) | 6.3 | 6.9 | 9.5 | 4.1 | 5.2 | 8.4 |
Cooling Mode Power (W) | 724 | 789 | 1,094 | 857 | 1,082 | 1,747 |
MCA (without Electric Heat) | 8.5 | 9.6 | 12.1 | 5.3 | 6.6 | 9.0 |
MOCP (without Electric Heat) | 15 | 15 | 15 | 15 | 15 | 15 |
MCA (with Electric Heat) | 16.7 | 17.2 | 17.2 | 18.5 | 21.5 | 18.5 | 21.5 | 26.3 | 18.6 | 21.6 | 26.5 |
MOCP (with Electric Heat) | 20 | 20 | 20 | 20 | 25 | 20 | 25 | 30 | 20 | 25 | 30 |
Airflow AC High Speed (CFM) | 380 | 380 | 400 | 380 | 400 | 540 |
Airflow AC Low Speed (CFM) | 300 | 300 | 350 | 300 | 350 | 450 |
Airflow Outside (CFM) | 60 | 60 | 60 | 60 | 60 | 60 |
Airflow Extra Outside (CFM) | 110 | 110 | 110 | 110 | 110 | 110 |
Weight Net/Ship (lbs) | 130/141 | 134/145 | 134/145 | 134/145 | 134/145 | 137/148 |
SPECIFICATION NOTES: 1. Cooling mode performance ratings are in compliance with AHRI standard 310/380 and CSA standard 744. 2. Heating mode performance ratings are in compliance with AHRI standard 310/380 and CSA standard 744. 3. Heat pump operation disabled below 38 °F (± 3 °F) 4. Optional can be motorized. 5. Performance data based on R32 green refrigerant. IMPORTANT: Additional voltages and alternate electric heat and heat pump options are available. For performance data and other available options please consult factory. Accessories are optional. Deviations from standard accessories may affect performance; louver requires 70% free area per original OEM specification; room enclosures must provide sufficient return air, free flowing supply air and must be properly sealed to prevent air recirculation; any non-standard components or accessories must be reviewed and approved by Ice Air or approved distributor. |