RSNU-HP – New Construction PTAC – Heat Pump

Product Info

ICE AIR RSNU-HP heat pumps with electric heat for new construction offers a durable, whisper-quiet solution with the highest energy efficiency available through the use of R-410A Green refrigerant.

ICE AIRs RSNU-HP unit is the perfect solution for new construction in a durable and user-friendly package.

Category: New Construction PTAC

Products: RSNU07, RSNU09, RSNU13, RSNU16, RSNU18

See all PTAC Products PTAC Accessories Thermostat Options

PTAC RSNU BIM/3D models

Ice Air - Product - PTAC - RSNU-HP - New Construction - Heat Pump

Specifications

SERIES MODEL # RSNU07 RSNU09 RSNU13 RSNU16 RSNU18
Total Cooling Capacity (Btu/hr)1 7,700 9,700 12,800 14,400 16,400
Sensible Cooling Capacity (Btu/hr)1 5,390 6,790 8,960 10,080 11,480
EER1 12.0 12.0 11.4 10.5 10.3
Heating Capacity (Btu/hr)2 7,200 8,700 11,500 13,300 15,200
COP2 3.40 3.30 3.30 3.13 3.13
Voltage 115 208/230 277 115 208/230 277 115 208/230 277 208/230 277 208/230 277
Electric Heater (kW)3 1.5 3.0 | 3.5 3.0 | 3.5 1.5 3.0 | 3.5 3.0 | 3.5 1.5 3.0 | 3.5 | 4.3 3.0 | 3.5 | 4.3 3.0 | 3.5 | 4.3 3.0 | 3.5 | 4.3 3.0 | 3.5 | 4.3 3.0 | 3.5 | 4.3
Electric Heater (A)3 13 14.4|16.8 10.8|12.6 13 14.4|16.8 10.8|12.6 13 14.4|16.8|20.7 10.8|12.6|15.5 14.4|16.8|20.7 10.8|12.6|15.5 14.4|16.8|20.7 10.8|12.6|15.5
Current in Cooling Operation (Amps) 5.6 3.1 2.3 7 3.9 2.9 9.8 5.4 4.1 6.6 4.9 7.7 5.7
Power in Cooling Operation (Watts) 642 808 1,123   1,592
MCA (without Electric Heat) 7 3.9 2.9 8.8 4.9 3.6 12.3 6.8 5.1 8.3 6.1 9.6 7.1
MOCP (without Electric Heat) 15 15 15 15 15 15 20 15 15 15 15 15 15
MCA (with Electric Heat) 17.6 18.8|21.8 14.2|16.4 17.6 18.8|21.8 14.2|16.4 17.6 18.8|21.8|26.6 14.2|16.4|19.9 18.8|21.8|26.6 14.2|16.4|19.9 18.8|21.8|26.6 14.2|16.4|19.9
MOCP (with Electric Heat) 20 20 | 25 15 | 20 20 20 | 25 15 | 20 20 20 | 25 | 30 15 | 20 | 20 20 | 25 | 30 15 | 20 | 20 20 | 25 | 30 15 | 20 | 20
Airflow – High Speed (CFM) 380 380 380 380 380 380 400 400 400 450 450 540 540
Airflow – Low Speed (CFM) 300 300 300 300 300 300 350 350 350 380 380 450 450
Outside Airflow (CFM) 60 60 60 60 60
O.A. with fan assist option (CFM) 110 110 110 110 110
Weight (Lbs.) 130 134 134 134 137
Specification Notes:
1. Cooling capacity rated @ EAT = 80/67 °F db/wb; Ambient = 95 °F db
2. Heating capacity rated @ EAT = 70/67 °F db/wb; Ambient = 47/43 °F db/wb
3. Heat pump operating disabled and electric heat enabled below 38°F (+/- 3 °F)